Falling Chainsaw creates Arc Flash

Thou shall not use an electrical room for storage!” We all know this rule as one of the electrical commandments, right? At least that’s what I thought. However, when I looked in the NEC, I couldn’t find it anywhere **. Upon further investigation, I realized it is actually not a Code requirement, but rather a good practice, as is noted in 110.26(B) and evidenced by the lesson in this forensic case study. It all started when an experienced electrician was dispatched to a big box store for what he thought was a typical service call. This was not his first visit to the store’s equipment room. On previous occasions, he’d operated circuit breakers at the facility but never removed any panel covers. This time was different.

Setting the Stage

The store manager was not happy because the ballasts in the fluorescent luminaires over the sales area were failing frequently. Because the main electrical room, which had two entrances, was locked, the manager had to unlock one of the doors for the electrician. The manager unlocked the interior door in the general back office area. The other door, which was equipped with an emergency push bar and opened to the outdoors, was located at the opposite end of the room. Although there was no sign posted on the door identifying it as an electrical equipment room, it was locked to prevent unauthorized entry.

The Accident

The electrician arrived on-site with his tool belt, hand tools, and gloves but no personal protective equipment (PPE). The company he worked for — a large regional electrical contractor —  just so happened to be in the process of issuing PPE to all of its workers. Previously, PPE was available for a minority of employees, generally provided on an “as-needed” basis if the worker reserved it ahead of time. Because this was a simple service call, the electrician hadn’t made arrangements to check out PPE. Although the electrician was trained to use the gear, he had never actually used it in the field — he’d only watched a video on proper usage.

The electrician proceeded to change out the ballasts. He did not switch the circuit breaker off prior to doing so because these units had plug-type disconnects that allow you to swap them out “hot.” After changing out the first ballast, the electrician checked the connection and voltage level at the 20A circuit breaker in the 277/480VAC lighting panel. He removed his tool belt and the panel cover, placing his clamp-on meter on the panel enclosure, which was located about 10 ft from the front door. He bent down in front of the panel, preparing to perform a visual examination when he heard the door open. The next thing he knew something was falling toward him.

Although he hadn’t noticed it upon entering the room initially, there was a shelving unit situated behind the door that held many storage items — one of which was a chain saw resting on the top shelf. As shown in Photo 1, notice how the door swings inward. Due to the substantial weight of the chain saw, the structure’s center of gravity produced a downward tipping force when it was hit by the opening door.

Reflexively, the electrician raised his right arm to protect his head when he saw the falling objects. The next thing he remembered he was sitting up against the panel cover, which was propped up by the main distribution cabinet (Photo 2). As shown in Photo 3, the chain saw struck the right bottom phase lug, resulting in arc flash damage to the red shield. The arc blast was heard in all offices.

The Aftermath

The electrician’s resulting injuries were more a result of the blast shock wave than burns. There was no evidence of classic electrical entry and exit wounds. EMS was called immediately, and the victim was transported to a specialty burn unit. Burns to the top of his head indicated that he was fortunately oriented face down at the time of the accident. Symptoms of blast-related traumatic brain injury (TBI) seemed to be the best fit for the electrician’s permanent impairment condition.

When I met the victim two years after the accident, he was still unable to walk without a brace, had no short-term memory, and was in rehab for stroke symptoms on his left side. His marriage had ended, and his future indicated lifetime support needs. Because the workman’s comp claim was insufficient to cover the victim’s extensive rehabilitation costs and loss of income, the electrician filed suit against the big box retailer. I was hired by the victim’s attorney to analyze the electrical forensic evidence in the case and determine the cause of the accident as well as liability.

The Investigation

At my initial site visit, I was accompanied by the electrician, his attorney, the defense attorney, employees of the electrician’s previous employer, and the store manager. The electrician’s former employer had an electrician with him who wore full PPE when removing the lighting panel cover and dead front, which covers exposed wiring to the breakers. After he finished removing the covers, the 200A circuit breaker feeding the lighting panel was turned off. We were told we were not allowed to approach within 5 ft of the panel while it was energized.

Now that the panel was de-energized, we asked the other parties to leave the room. This left me, the electrician, and the lawyer. Once the other parties had vacated, I asked the electrician to place his clamp-on meter where it was at the time of the accident and show me where and how he was positioned. Working with this information, I could establish a theory of how the chain saw fell and was ultimately deflected by his right arm into the panel. This would have put the impact point area at the bottom of the panel, which was the feeder location.

After lifting the arc shield, I could see the orientation of cables at the bottom of the panel. I was also able to match up the damage to the chain saw to the panel. Given the amount of smoke char to the back of the shield, I concluded the chain saw fault was between the line and ground. This placed the electrician about 2 ft to 3 ft in front of the arc flash location.

Independent and store incident investigations confirmed that at the time of the accident there was an electric chain saw resting on the top shelf of the 5-ft plastic sectional shelving unit adjacent to the interior door. Paint cans were also stored on lower shelves, as shown in Photo 4. The damage I observed to the chain saw obviously had to come from contact with an energized source, as shown in Photo 5. Unfortunately, the chain saw had been lost and never located, although it was being held as evidence (according to the store manager).

My examination of damage to the chain saw bar based on a single image from the scene indicated arc damage at two points consistent with contact with the lug and grounded cabinet. I marveled at the small probability of how the original and deflected fall trajectory resulted in coincidental alignment with the shield edge.

Who Done It?

Despite these conclusions, one question remained: Who opened the door? The electrician was able to recall a familiar-looking woman opening the door prior to the impact; however, deposition testimony did not reveal the responsible party. There were several women working in adjacent offices who were aware someone was working in the electrical room. My working theory was that one of these women opened the door to check on the electrician or see what was going on. In the process of doing so, the door struck the shelf, causing the unit to tip over and launching the chain saw toward the victim.

Forensic Analysis

Clearly, the store had violated a number of its own policies that expressly prohibited using an electrical room for storage. Store policy also required shelves loaded with the heaviest objects at the bottom, which effectively lowers the center of gravity. Had the chain saw been located on the bottom shelf per store requirements, this accident would not have occurred.

It was discovered during deposition testimony that the chain saw was used to trim Christmas trees — and had been stored in the electrical room for quite some time. There was no question that the chain saw was stored in violation of store policy with respect to its presence and location. The fact that the chain saw disappeared post accident did not help the defendant’s case either.

Legal Arguments

The store’s litigation team argued that if the electrician had been using appropriate PPE he would not have been injured. Although I agreed that PPE would have protected him from burns, I argued it would not have prevented the shock wave injuries and resulting TBI. In the end, the case settled out of court in favor of the victim for an undisclosed amount prior to trial.

Lessons Learned

The moral of this story is that even innocuous storage in an electrical room should not be allowed and always reported to management. Of course, we know this happens all too frequently. After seeing the results of this improbable accident, I know I will always admonish responsible parties to remove any and all stored items from electrical rooms. In the end, your willingness to follow this unwritten electrical commandment may save your life and the lives of others.

BLOGGER’S NOTES:  ** This arc flash article originally from ECM seems to have a particular bias to it, has some improper information and ignores some key electrical safety requirements.

The opening paragraph about NEC and clear spaces not being a requirement, but rather just a good practice is incorrect and it also ignores OSHA federal laws and NFPA 70E standards.   OSHA, NEC and and NFPA 70E all have this is a requirement as “shall”, not as a “good practice”.  Work space is one of the most common citations by OSHA and all states have adopted work space around electrical equipment as part of their own electrical code if different from NEC.  Pictures were provided in the article.  From the pictures, it would appear the shelving was violating the work space, and the door itself might also violate the workspace.  The door would also violate NEC 110.26(C)(3) if the equipment was rated 1200A + and NFPA 70E 130.6 (G) as the door clearly created a hazard.

Prior to beginning the work, the worker should have done a Pre – Job Hazard assessment and if so he should have identified the hazards in the room and  cleared the hazards before removing the cover.

Further, he should have followed proper alerting techniques and either blocked the area with warning signs and caution tape to prevent access to the area or assigned an attendant to watch the door.

While the article here tries to define the storage room as the culprit, following electrical safety practices as outlined in NFPA 70E would have most likely eliminatd this accident.

Story via ecmweb.com

For Arc Flash Analysis  and Electrcial Safety Training services visit:

Martin Technical Electrical Safety Services Arc Flash

Advertisement – Click on Ad to visit Martin Technical

Arc Flash in FL Injures Electrician

December 16, 2011 Leave a comment

NAPLES, FL — An electrician is being treated at the hospital after suffering extensive burns during an electrical explosion at a Naples resort.  The explosion was most likely the result of an arc flash.

The Naples Daily News reports 24 hotel guests and 20 employees were evacuated from the Naples Bay Resort Thursday morning.

Fire rescue says the electrician was working in the second floor meter room when an electrical fault occurred, producing a fireball that severely burned his face and right side of his body. He was treated at the scene by firefighters before being taken to the hospital.

Story via OrlandoSentinnel.com

 

Free Electrical Safety Resources Martin Technical Arc Flash

Click Logo for Free Resources

 

2 Electricians Shocked Working on Panel in MA

December 15, 2011 Leave a comment

Norton, MA – Earlier today, fire and rescue officials were deployed to Horizon Beverage facility, located at 45 Commerce Way, Norton, for two electricians who were injured by an electrical shock.

Both men, who were working on an electrical panel, were taken to area hospitals for treatment of electrical burns.

According to reports by Sun Chronicle, fire captain Shawn Simmons said that one worker suffered  second-degree burns to his face and another suffered minor burns. The victims were subcontractors at the site  and  were not employees of Horizon Beverage, Simmons said.

One worker has since been treated and released; the other remains hospitalized.

The exact cause of the accident is under investigation.

“Our thoughts are with the injured men and their families,” said vice president of operations Michael Epstein.

Story via NortonPatch.com

Electrical Safety Programs and Consulting

Martin Technical Electrical Safety Services Arc Flash

Advertisement - Click on Ad to visit Martin Technical

Electrician Injured at Page Field Airport

January 22, 2011 Leave a comment

Fort Meyers, FL – One person has been transported to Lee Memorial Hospital following an electrical accident at Page Field Airport in Fort Myers.

Patrick Conran, spokesman for general contractor Owen-Ames-Kimball, said there was an electrical accident and an injury to one of the company’s electricians, but Conran didn’t yet know what happened.

 He said he was on his way to Page Field to get more information on the incident.

Story via News-Press.com

Martin Technical Electrical Safety Service

Advertisement - Click on Ad to visit Martin Technical

Electrician Killed on Job Repairing Street Light

January 6, 2011 Leave a comment

Northampton, UK – A HEALTH and safety investigation has been launched following the death of an electrician who was killed while carrying out a routine job yesterday.

It was thought Christopher Partridge, aged 55, from Northampton, was electrocuted as he fixed a street light inside the entrance of Blisworth Park, a mobile home site in Blisworth Arm.

He fell from a ladder yesterday lunchtime and hit his head on the ground, where he was pronounced dead by police.

Police cordoned off the area while representatives from Environmental Health and the Health and Safety Executive began an investigation.

The man had been an electrician for 15 years on-and-off at the site, which houses around 80 homes.

Detective Sergeant Tony Barsby, in charge at the scene, said: “The deceased was an electrician and had been working with another man who was holding the bottom of the ladder at the time.

“He had gone up the ladder to repair a light, when for reasons unknown, the light sparked and electrocuted him. He fell down and hit his head on the kerb.

“We are treating it as non-suspicious. It was a tragic accident.”

South Northants Council confirmed that an investigation into the death is now being carried out.

A spokesman said: “We are carrying out an investigation into this tragic incident and our heartfelt thoughts go out to the family and friends of the deceased.

“The investigation involves taking witness statements, assessing what happened and making sure the site is immediately safe.

“Our priority is to make sure this does not happen again, determine if there was a breach of any health and safety laws, and implement our enforcement policy if necessary.

“As this is an ongoing investigation, it would be inappropriate to comment further at this time.”

A shocked resident said the death was likely to upset neighbours who had grown close with the park’s staff.

Janet Smith, aged 48, said: “It’s awful news.

“We are a close community here, and it is a lovely quiet area.

“This is a real shock and it will be very saddening to all the neighbours here.”

Story via NorthHamptonChron.co.uk

Man Electrocuted in TX Working on Utility Pole

December 30, 2010 Leave a comment

GOLIAD, TX – Bonnie Hennig will always remember her 48-year-old son as a handyman of sorts.

Hennig’s son, Lacy McDonald, of San Antonio, was killed instantly on Dec. 19 when he was electrocuted by nearly 30,000 volts of electricity while trying to disconnect power on a utility pole at the Fair Oaks Village Shopping Center in San Antonio, said Christine Patmon, manager of news media and public relations of CPS Energy, the company that owned the pole.

McDonald, of San Antonio, was a self-employed electrician and not an employee of CPS Energy, Patmon said.

“It was an unfortunate incident,” Patmon said.

McDonald did not call the energy company to have the electricity shut off, she added.

McDonald was installing electricity for a business at the shopping center, Fair Oaks Ranch Police Chief Scott Rubin said.

Rubin was unsure of the business’s name.

Those were the answers Hennig had been looking for.

At first, she said she was unaware if he had called to have the power shut off.

“Pointing fingers and stuff like that won’t bring him back,” she said.

The 1980 graduate of Victoria High School had worked in electricity and construction since high school, McDonald’s mother said.

He had recently remarried and had two children and two stepchildren, she added.

McDonald had lived in San Antonio for the past 30 years.

“You just shouldn’t have to bury your children and write their obituary,” she said

story via Victoria Advocate.com

PA Man Electrocuted Working at Regency Tower Apartments

November 1, 2010 Leave a comment

MONTGOMERY, PENNSYLVANIA – Residents of the Regency Towers Apartments, 1003 Easton Road, Willow Grove, experienced a partial power outage Oct. 29 after a 36-year-old electrician was electrocuted while work on the buildings’ electrical breakers, police said.

The Upper Moreland Police Department, the Willow Grove Fire Co. and Second Alarmers Rescue Squad responded to the scene, police said, adding that the victim was conscious and standing when emergency personnel arrived. He was treated immediately by Second Alarmers and flown to Temple University Hospital where he was treated and released.

There was no fire so evacuation of the nine-story building was not necessary, police said.

Story via MontgomeryNews.com